1600-KVA

3-Phase hermetically sealed oil immersed distribution transformers technical specification

Description Unit Particulars
Rated Power KVA 1600
HV & LV winding material Copper
Applied Standard IEC 60076
Primary Voltage KV 20
Secondary Voltage (at No-load) KV 0.4
Rated Primary Current A 46.19
Rated secondary current A 2309.4
Frequency Hz 50
Vector Group Dyn11
Voltage Regulation % ±2 * 2.5%
Maximum Ambient Temperature °C 50
Maximum Temperature Rise for oil °C 50
Maximum Temperature Rise for winding °C 55
No-load losses (W) 2200
Copper losses (at 75 °C) (W) 14000
Impedance Voltage (IEC Tolerance Applied) % 6
Transformer Type Hermetically Sealed
Cooling Method ONAN
Weight of oil kg 620
Total weight of transformer kg 3645
Over all Dimensions Length x Width x Height mm 1870 x 1180 x 1800

Tolerance in dimensions and weights ±10 %

For more capacities, please contact us

MORE PRODUCTS