200-KVA
3-Phase hermetically sealed oil immersed distribution transformers technical specification
Description | Unit | Particulars |
---|---|---|
Rated Power | KVA | 200 |
HV & LV winding material | Copper | |
Applied Standard | IEC 60076 | |
Primary Voltage | KV | 20 |
Secondary Voltage (at No-load) | KV | 0.4 |
Rated Primary Current | A | 5.77 |
Rated secondary current | A | 288.68 |
Frequency | Hz | 50 |
Vector Group | Dyn11 | |
Voltage Regulation | % | ±2 * 2.5% |
Maximum Ambient Temperature | °C | 50 |
Maximum Temperature Rise for oil | °C | 50 |
Maximum Temperature Rise for winding | °C | 55 |
No-load losses | (W) | 500 |
Copper losses (at 75 °C) | (W) | 2400 |
Impedance Voltage (IEC Tolerance Applied) | % | 4 |
Transformer Type | Hermetically Sealed | |
Cooling Method | ONAN | |
Weight of oil | kg | 180 |
Total weight of transformer | kg | 1020 |
Over all Dimensions Length x Width x Height | mm | 1260 x 825 x 1390 |